ALLEM SECURITY

centrale conventionnel extensible

Dans votre sélection Ajouter à ma sélection  |  Imprimer  |  Envoyer à un ami  |  Retour aux résultats
   » Alarmes intrusions    »  Publié le 2014-06-02  [Lu  5244  fois]


FIRE ALARM LINES


- Maximum number of fire detectors in a line
32

- Connecting line
two-wire

- Maximum resistance of a line
100Ω

CONTROLLABLE OUTPUTS


- Type
Potential

- Electrical characteristics
(24±5)V/500 mA

RELAY OUTPUTS FOR FAULT CONDITIONS

- Type
potential free, switching

- Electrical characteristics
3 A/125 V AC; 3 A/30 V DC

RELAY OUTPUTS FOR FAULT CONDITIONS

- Type
potential free, switching

- Electrical characteristics
3 A/125 V AC; 3 A/30 V DC

INDICATIONS OF REGISTERED EVENTS


- Light indication
LEDs

- Text messages
LCD display - 4 lines, 20 symbols,
Latin/Cyrillic characters, backlit

- Sound
Built-in sounder

ACCESS LEVELS TO CONTROL FUNCTIONS
4 (in compliance with EN 54/2)

POWER SUPPLY


- Voltage
220/230 V

- Frequency
50 Hz

BACKUP BATTERIES
2 x 12 V / 12 Ah

OPERATION IN DUTY MODE UPON INTERRUPTED MAINS SUPPLY

- Minimum configuration
80 h

- Maximum configuration
30 h

CONSUMPTION ON BACKUP BATTERIES SUPPLY IN DUTY MODE AT 24 V

- Minimum configuration
<155 mA

- Maximum configuration
<400 mA

POWER SUPPLY TO EXTERNAL DEVICES

- Voltage
(24±5)V

- Maximum current value (current of controllable outputs included)
1,5 A

WEIGHT (BACKUP BATTERIES NOT INCLUDED)
6,6 kg

DIMENSIONS
450 x 355 x 115mm

OPERATING TEMPERATURE
-5 oC to +40 oC

RELATIVE HUMIDITY
to 93 %

DEGREE OF PROTECTION



 

 Sujet :
 Message :
Décrivez votre besoin...
 
Diffusez cette demande à d'autres fournisseurs
 E-mail :
 
 

Accueil | Présentation | Information générale | Contact | Catalogue produits | Actualités
 
Made-in-tunisia.net